Testing a Class II appliance is a shorter sequence than testing a Class I one, and it is not the same sequence with a step removed. A Class II appliance has no protective earth. It is built with two layers of insulation, one around the internal wiring and one around the casing, and that second layer does the job an earth connection does elsewhere.

class II Appliances PAT testing method

The test method follows from that: a formal visual inspection, an insulation resistance test, a touch current measurement where the insulation test cannot give a usable result, and no earth continuity test at any point. This article covers the symbol that identifies the class, the method step by step, the pass limits, the probe placement problem on fully enclosed appliances, and what the sequence actually finds. For the classes themselves, see our guide to the types of electrical appliances that need PAT testing.

How Is a Class II Appliance PAT Tested?

A Class II appliance is PAT tested in three steps: a formal visual inspection, an insulation resistance test, and a touch current test where the insulation resistance test cannot be applied. The result is then recorded against the appliance.

A formal visual inspection is a structured check of the appliance, its flex and its plug, carried out before any electrical test. It is not a glance. It can fail the appliance on its own, and roughly the majority of faults found during in-service testing are found at this stage rather than by an instrument.

class II testing-method three step sequence

The full sequence runs:

  • Inspect the appliance, flex and plug formally, before connecting anything
  • Test the insulation resistance between the mains conductors and the casing
  • Measure the touch current where the insulation resistance test cannot be applied or cannot be trusted
  • Record the reading, the result and the date against the appliance

The sequence depends on correctly identifying the class, and there is a mark for that.

Which Symbol Identifies a Class II Appliance?

A Class II appliance carries a double square symbol: one square inside another. It is the standard international mark for double insulated construction.

The mark is found on the rating plate, moulded into the plastic casing, or printed on the plug top of some moulded leads. It is small, and on a worn appliance it is often the clearest surviving indicator of the class.

Which Symbol Identifies a Class II Appliance?

The absence of an earth pin is a supporting indicator and not proof. Many UK moulded plugs on Class II equipment carry a plastic dummy earth pin, which is there to open the socket shutters rather than to conduct anything. A metal-cased appliance can also be Class II, because the class describes the construction rather than the material of the housing. The symbol settles it; the appearance does not.

Once the class is confirmed, the first electrical test follows.

How Is the Insulation Resistance Test Carried Out on a Class II Appliance?

The insulation resistance test applies a DC voltage between the appliance’s live and neutral conductors, joined together, and a probe placed on the appliance casing. It measures how well the insulation separates the mains conductors from anything a person can touch.

The standard test voltage is 500 V DC. The appliance is switched on where it has a switch, so that the test reaches the internal wiring beyond the switch rather than stopping at it. The voltage is applied for a few seconds and the tester displays a resistance reading in megohms, a megohm being one million ohms.

class II testing-method insulation-test connection

What the reading describes is a barrier. On a Class I appliance, insulation failure is a problem partly because the earth connection is there to deal with it. On a Class II appliance there is no earth connection, so the insulation is the whole of the protection, and the reading is a direct measure of how much of that protection is left.

The measurement needs a figure to be judged against.

What Is the Pass Limit for a Class II Insulation Resistance Test?

The pass limit for a Class II insulation resistance test is at least 2 MΩ, measured at 500 V DC.

That is twice the Class I figure of at least 1 MΩ, and the reason is the one already given: a Class II appliance has no protective earth behind the insulation, so more is asked of the insulation itself. A reading below 2 MΩ on a Class II appliance is a fail, and the appliance comes out of service pending repair or replacement.

class II testing method insulation-pass limit

The figure assumes the probe can be placed somewhere, and on a great many Class II appliances it cannot.

Where Does the Probe Go on an Appliance With No Exposed Metal?

On an appliance with no exposed metal, the probe is placed against the casing at several points in turn rather than on a single contact. Each position gives its own reading, and the lowest reading is the one that counts.

The positions worth taking are the ones where the inside comes closest to the outside: seams and joints in the moulding, ventilation slots, screw heads, control spindles, metal trim, the cord grip where the flex enters the body, and any metal fitting such as a blade guard or a shaft. On a fully enclosed plastic appliance with none of these, the test has nothing conductive to measure to, and a very high or open reading in that situation confirms that the probe touched plastic rather than that the appliance is sound.

class II testing method probe positions

That is the case where the formal visual inspection carries most of the judgement, and it should be correspondingly thorough: the flex along its whole length, the cord grip at both ends, the plug interior where the plug is rewireable, the casing for cracks, and the appliance for signs of overheating. An instrument reading does not replace any of that.

Where the insulation resistance test cannot give a usable result, a second measurement is available.

When Is a Touch Current Test Used Instead?

The touch current test is used where the insulation resistance test cannot be applied or cannot be trusted. Touch current is the current that would pass through a person touching the appliance while it is running.

There are two common cases. The first is electronic equipment with surge protection, where the protective components present a low resistance at 500 V DC and produce a fail on an appliance that is sound. The standard response is to repeat the test at 250 V DC, which most testers offer as a setting. The second is equipment where no meaningful insulation resistance reading can be obtained at all.

class II testing-method touch current limit

The touch current test works differently. The appliance is run at mains voltage and the tester measures the current flowing from the casing through a 2 kΩ resistor, which stands in for the resistance of a human body. The 5th Edition of the IET Code of Practice sets a limit of 5 mA for that measurement, and the same 5 mA figure now applies across equipment types in place of the lower class-dependent values used in earlier editions.

The appliance is energised during this test. That is the practical reason it belongs to somebody who has been trained rather than to somebody working through a tester’s menu.

Why Does a Class II Appliance Get No Earth Continuity Test?

A Class II appliance gets no earth continuity test because it has no protective earth to test. The test measures the resistance of a path that does not exist on this class of equipment.

The mechanism is worth stating once. A Class I appliance relies on an earth connection to carry a fault current safely to ground if the basic insulation fails, and the earth continuity test confirms that the path from the plug’s earth pin to the appliance casing is intact. A Class II appliance is built so that no single insulation failure can make the casing live, which is what the second layer of insulation is for, and there is therefore no protective path to verify.

class II testing method class I vs class II

One exception has a name. The 5th Edition recognises Class II FE: equipment with a functional earth, connected for a reason such as electromagnetic compatibility rather than for protection. IT power supplies are the common example. A functional earth is not a protective earth, and it is not tested as one.

For the other side of the comparison, see how Class I appliances are PAT tested.

The sequence is short. What it finds is the part worth knowing.

Which Class II Faults Does PAT Testing Actually Find?

The Class II sequence finds faults in the insulation and in the flex, and it finds them in roughly that order of frequency. The list below covers what turns up repeatedly in service.

  • Damaged casings, including cracks, impact damage and missing covers that expose internal wiring
  • Flex damage at the two points it always happens: where the flex enters the appliance body, and where it enters the plug
  • Moisture ingress, including appliances that read low after storage in an unheated space and recover after being run
  • Insulation degradation from heat, common in appliances with motors or heating elements that have been run hard
  • Incorrect repairs, where a previous fix has introduced a conductive path between the inside and the outside

class II testing method faults found and missed

What the sequence does not find is a fault that only appears under mechanical load, at operating temperature, or after the appliance has been moved. That is a limit of in-service testing generally rather than of the Class II method in particular, and it is why retest intervals exist.

Knowing what a reading means is the skill, and it is the part a course teaches.

How a Course Covers the Class II Test Sequence

Training covers the Class II sequence as a sequence, including the cases where the standard test gives an unusable reading and the operator has to decide what to do next.

The Live Online PAT Testing Course is tutor-led via Zoom rather than pre-recorded, runs for one day, and costs £145 +VAT. It follows the IET 5th Edition curriculum and includes practical elements with hands-on testing rather than theory alone. It ends in a UKRS-accredited Certificate of Competence, and it comes with lifetime learning zone access, lifetime after-course support, and the free PAT Reporter app for recording results and producing reports.

If the probe placement problem above is the kind of thing you would rather ask a tutor about than guess at, that is what the online PAT testing course is for.

Do Class II Appliances Need PAT Testing?

Yes. Double insulation reduces the chance of a fault reaching the user, and it does not remove the chance of the insulation itself failing. The duty to maintain electrical equipment so as to prevent danger applies to the appliance whatever its class, and the inspection and test regime follows from that duty rather than from the construction.

Can a Class II Appliance Pass Insulation Resistance and Still Be Unsafe?

Yes. The insulation resistance test measures one property at one moment. A cracked casing, a frayed flex at the cord grip, a damaged plug or signs of overheating fail the appliance at the formal visual inspection, and no electrical reading overrides that result. This is the reason the visual inspection comes first in the sequence rather than last.

 

 